Description

Product Overview

The Spirax Sarco HM34 Series is a carbon steel inverted bucket steam trap. It discharges condensate from horizontal steam systems to prevent waterlogging and maintain thermal efficiency. The trap incorporates an internal strainer as standard and is rated for saturated steam service up to 32 bar g.

Key Features

  • Manufactured with a carbon steel body (forged steel for 1/2” and 3/4” sizes, cast steel for 1” size).
  • Integral stainless steel strainer screen fitted as standard.
  • Designed specifically for horizontal pipeline installations.
  • Complies with the requirements of the Pressure Equipment Directive 2014/68/EU.
  • Available with certification to EN 10204 2.2 upon request.

Technical Specifications

ParameterValue
Sizes1/2”, 3/4”, 1” (DN15, DN20, DN25)
Pipe ConnectionsScrewed BSP T Rp (ISO 7-1) or NPT; Socket weld ends BS 3799 Class 3000; Flanged EN 1092 PN40, ANSI 150, ANSI 300
Body Design ConditionsPN40
PMA (Maximum Allowable Pressure)40 bar g @ 120 °C (580 psi g @ 248 °F)
TMA (Maximum Allowable Temperature)300 °C (572 °F)
Minimum Allowable Temperature-10 °C (14 °F)
PMO (Maximum Operating Pressure)32 bar g (464 psi g) for saturated steam
TMO (Maximum Operating Temperature)300 °C (572 °F)
Minimum Operating Temperature0 °C (32 °F)
Maximum Cold Hydraulic Test Pressure60 bar g (870 psi g)

Spirax Sarco HM34 Series operating range chart

Maximum Differential Pressure (ΔPMX)

Size4 bar (58 psi)8.5 bar (123 psi)12 bar (174 psi)20 bar (290 psi)32 bar (464 psi)
DN15 - 1/2”HM34/8HM34/7HM34/6HM34/5HM34/4
DN20 - 3/4”HM34/10HM34/8HM34/7HM34/6HM34/5
DN25 - 1”HM34/12HM34/10HM34/8HM34/6HM34/5

Materials

Spirax Sarco HM34 Series 1/2 inch and 3/4 inch cross section

Spirax Sarco HM34 Series 1 inch cross section

PartMaterialSpecification
Cover (1/2”, 3/4”)Forged steel1.0460 (C22.8)
Cover (1”)Cast steel1.0619 +N
BodyCast steel1.0619 +N
BucketStainless steelBS 1449 304 S31
Valve guide plateStainless steelBS 1449 304 S11
Cover gasketReinforced exfoliated graphite
Valve seatStainless steelAISI 431
ValveStainless steelAISI 440B
Valve leverStainless steelBS 1449 321 S31
Strainer screenStainless steelASTM A240 316L
Strainer capSteel1.0460 (C22.8)

Applications

  • Steam systems (Group 2 fluids)
  • Air systems
  • Water and condensate systems

Installation Notes

The trap must be installed with the body upright so that the bucket rises and falls vertically. The inlet and outlet connections should be in a horizontal plane, with the trap installed below the drain point to maintain a water seal around the open end of the bucket. A small drop leg (typically 150 mm) should precede the trap.

Spirax Sarco HM34 Series installation diagram with U seal

If the trap must be installed at a higher point than the drainage point, a small bore riser into a ‘U’ seal should be used, and a check valve should be fitted before the trap to prevent the loss of the internal water seal. Inverted bucket steam traps do not permit rapid release of air; on process applications, a separate external air vent is required in parallel.

WeChat ID copied